Guide to Low Voltage Panel Separation

Click a form of separation for the guide classifications:

Form 4 Separation of busbars from the functional units, and separation of all functional units from one another, including the terminals for external conductors which are an integral part of the functional unit.
Type 1 Terminals for external conductors located in the same compartment as the associated functional unit. Busbar separation is achieved by insulated coverings, eg. Sleeving, wrapping or coatings. Cables may be glanded elsewhere.
Type 2 Terminals for external conductors located in the same compartment as the associated functional unit. Busbar separation is achieved by metallic, or non-metallic, rigid barriers, or partitions. Cables may be glanded elsewhere.
Type 3 Terminals for external conductors located in the same compartment as the associated functional unit. Busbar separation is achieved by insulated coverings, eg. Sleeving, wrapping, or coatings. The termination for each functional unit has its own integral glanding facility.
Type 4 Terminals for external conductors located in the same compartment as the associated functional unit, but in individual, separate, enclosed protected spaces, or compartments. Busbar separation is achieved by insulated coverings, eg. Sleeving, wrapping or coatings. Cables may be glanded elsewhere.
Type 5 Terminals for external conductors located in the same compartment as the associated functional unit, but in individual, separate, enclosed protected spaces, or compartments. Busbar separation is achieved by metallic, or non-metallic, rigid barriers, or partitions. Terminals may be separated by insulated coverings, and glanded in common cabling chambers.
Type 6 Terminals for external conductors located in the same compartment as the associated functional unit, but in individual, separate, enclosed protected spaces, or compartments. All separation is by metallic or non-metallic, rigid barriers, or partitions. Cables are glanded in common cabling chamber.
Type 7 Terminals for external conductors located in the same compartment as the associated functional unit, but in individual separate, enclosed protected spaces, or compartments. All separation is by metallic, or non-metallic, rigid barriers, or partitions. The termination for each functional unit has its own integral glanding facility.

circuit diagram

circuit diagram

circuit diagram

circuit diagram

circuit diagram

Note: These forms of separation are not relevant to arc fault containment which is not the subject of this specification, and would be subject to agreement between the manufacturer, and the client.

If you would like more information on Sandford Electrical industrial control systems products and services please call 01628 668 808 or contact us.

 

 

home | about us | contact us | why sandford? | technical help & information | products | services | industry sectors | onsite modification and upgrades | clients | case studies | disclaimer | HVAC control systems | cookies | site map

Sandford Electrical Services
Unit 2, Kelpatrick Road, Cippenham, Slough, Berks, SL1 6BW, UK
Tel: 01628 668 808 | Fax: 01628 668 809 | E-mail: sales@sandfordelectrical.co.uk

  ? Copyright 2005 Sandford Electrical Control Systems and its licensors - All Rights Reserved